Power systems miscellaneous
- A medium line with parameters A, B, C, D is extended by connecting a short line of impedance Z in series. The over all ABCD par ameters of the series combination will be
-
View Hint View Answer Discuss in Forum
A B = A1 B1 C D C1 D1
For a short line, A = 1, B = Z, C = 0, D = 1
∴ Resultant parameters are given byAT BT = A B CT DT C D 1 Z = A AZ + B 0 1 C CZ + D Correct Option: B
A B = A1 B1 C D C1 D1
For a short line, A = 1, B = Z, C = 0, D = 1
∴ Resultant parameters are given byAT BT = A B CT DT C D 1 Z = A AZ + B 0 1 C CZ + D
- A single phase transmisson line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is
-
View Hint View Answer Discuss in Forum
VS = Vr + IZs
= 300 + j 0.8 × [500 × 0.8 – 500 × 0.6]
= 300 + j 0.8 [400 – j 300]
= 300 + j 320 + 240 = 540 + j 320= 320 = 0.6 lag 500 Correct Option: D
VS = Vr + IZs
= 300 + j 0.8 × [500 × 0.8 – 500 × 0.6]
= 300 + j 0.8 [400 – j 300]
= 300 + j 320 + 240 = 540 + j 320= 320 = 0.6 lag 500
- Which one of the following statements is not correct for the use of bundled conduct or sin transmission lines?
-
View Hint View Answer Discuss in Forum
NA
Correct Option: D
NA
- For equilateral spacing of conductors of an untrasposed 3-phase line, we have
-
View Hint View Answer Discuss in Forum
NA
Correct Option: C
NA
- The yearly load duration curve of a power plant is a straight line. The maximum load is 750 MW and the minimum load is 600 MW. The capacity of the plant is 900 MW. What is the capacity factor and utilization factor?
-
View Hint View Answer Discuss in Forum
Average Annual load = 750 + 600 = 675 MW 2 Capacity factor = Average Annual load = 675 = 0.75 Capacity of the Plant 900 Utilization factor = Maximum demand = 750 = 0.83 Capacity of the plant 900 Correct Option: B
Average Annual load = 750 + 600 = 675 MW 2 Capacity factor = Average Annual load = 675 = 0.75 Capacity of the Plant 900 Utilization factor = Maximum demand = 750 = 0.83 Capacity of the plant 900