- The incremental cost character istics of two generators delivering 200 MW are as follows:
dF1 = 2.0 + 0.01P1; dP1 dF2 = 1.6 + 0.2 P2; dP2
For economic operation, the generations P1 and P2 should be
-
View Hint View Answer Discuss in Forum
P1 + P1 = 200
and dF1 = dF2 dP1 dP2 Correct Option: D
P1 + P1 = 200
and dF1 = dF2 dP1 dP2
- A synchronous generator connected to infinite bus delivers power at a log p.f. If its excitation is increased
-
View Hint View Answer Discuss in Forum
NA
Correct Option: D
NA
- A 100 kVA transformer has 4% impedance and 50 kVA transformer has 3% impedance when they are operated in parallel, which transformer will reach full load first
-
View Hint View Answer Discuss in Forum
Z1 < Z2 S2(rated) < 0.03 × 50 S1(rated) 100 Z1 < Z2 S1(rated) S2(rated) 0.03 < 0.04 × 100 < 0.08 50 Correct Option: A
Z1 < Z2 S2(rated) < 0.03 × 50 S1(rated) 100 Z1 < Z2 S1(rated) S2(rated) 0.03 < 0.04 × 100 < 0.08 50
- A shunt reactor at 100 MVAr is operated at 98% of its rated voltage and at 96% of its rated frequency. The reactive power absorbed by the reactor is
-
View Hint View Answer Discuss in Forum
Reactive Power = V² = V² Xs 2πƒL Preact = 0.98V × 0.98V / V² 2πL × 0.96ƒ 2πƒL = 0.98 × 0.98 × 100 0.96
= 100.04 MVArCorrect Option: D
Reactive Power = V² = V² Xs 2πƒL Preact = 0.98V × 0.98V / V² 2πL × 0.96ƒ 2πƒL = 0.98 × 0.98 × 100 0.96
= 100.04 MVAr