Power systems miscellaneous


  1. Four identical alternators each rated for 20 MVA, 11 KV having a subtransient reactance of 16% are working in parallel. The short-circuit level at the bus bars is _______ MVA









  1. View Hint View Answer Discuss in Forum

    Short circuit capacity =
    Rating of circuit
    % X

    =
    20
    = 500 MVA
    %4

    Correct Option: B

    Short circuit capacity =
    Rating of circuit
    % X

    =
    20
    = 500 MVA
    %4


  1. A power system network with the capacity at 100 MVA has a source impedance at 10% at a point. The fault at that point is __________ MVA









  1. View Hint View Answer Discuss in Forum

    Fault MVA =
    Capacity
    % of reactance

    =
    100
    = 1000 MVA
    0.10

    Correct Option: A

    Fault MVA =
    Capacity
    % of reactance

    =
    100
    = 1000 MVA
    0.10



  1. The positive sequence current for a L-L fault of a 2 kV system is 1400 A, and corresponding current for a L-L-G fault is 2220 A. The zero sequence impedance of the system is ________ Ω









  1. View Hint View Answer Discuss in Forum

    NA

    Correct Option: D

    NA


  1. Four identical 100 MVA, 22 kV generators are operating in parallel, as shown above in two busbar sections, interconnected through a current limiting reactor of x p.u. reactance on the generatorbase. Each generator has a reactance of 0.2 p.u. The value of the reactor x to limit a symmetrical short-circuit (a-b-c) current p.u. through the circuit breaker to 1500 MVA is _________ p.u.









  1. View Hint View Answer Discuss in Forum

    (SC)MVA in p.r. =
    1500
    = 15
    100

    Now, 15 =
    1
    ⇒ 15 =
    0.2 + x
    = 1.25
    (0.1 + x)0.1
    (0.1 + x)0.1
    (0.2 + x)

    ⇒ 1.5x + 0.15 = 0.2 + x
    x = 0.10 p.u.

    Correct Option: C

    (SC)MVA in p.r. =
    1500
    = 15
    100

    Now, 15 =
    1
    ⇒ 15 =
    0.2 + x
    = 1.25
    (0.1 + x)0.1
    (0.1 + x)0.1
    (0.2 + x)

    ⇒ 1.5x + 0.15 = 0.2 + x
    x = 0.10 p.u.



  1. A 50 Hz alternator is rated 500 MVA, 20 kV, with Xd = 1.0 per unit and X"d = 0.2 per unit. It supplies a purely resistive load of 400 MW at 20 kV. The load is connected directly across the generator terminals when a symmetrical fault occurs at the load terminals. The initial rms current in the generator in per unit is __________









  1. View Hint View Answer Discuss in Forum

    NA

    Correct Option: B

    NA