Power systems miscellaneous


  1. If a 100V/10V, 50 VA transformer is converted to 100/110V auto transformer, then rating of the auto transformer is _______ VA









  1. View Hint View Answer Discuss in Forum

    NA

    Correct Option: D

    NA


  1. A transformer rated for 500 kVA. 11 kv/0.4 kV has an impedance at 10% and is connected to an infinite bus. The fault level of the transformer is ___________ kVA









  1. View Hint View Answer Discuss in Forum

    NA

    Correct Option: B

    NA



  1. A 100/5 A bar primary current transformer supplies an O/C relay set at 25% pick up and it has a burden at 5 VA. The secondary voltage is _________V









  1. View Hint View Answer Discuss in Forum

    NA

    Correct Option: A

    NA


  1. If the inductance and capacitance of a system are 1 H and 0·01 μF respectively and the instantaneous value of current interrupted is 10 amps. The value of shunt resistance across the breaker for critical damping is ________ kΩ









  1. View Hint View Answer Discuss in Forum

    For critical damping,

    R = 0.5 √
    L
    = 0.5√
    1
    = 5 kΩ
    C0.01 × 10-6

    Correct Option: C

    For critical damping,

    R = 0.5 √
    L
    = 0.5√
    1
    = 5 kΩ
    C0.01 × 10-6



  1. If the inductance and capacitance of a system are 1·0 H and 0·01 μF respectively and the instantaneous value of current interrupted is 10 amp, the voltage across the breaker contacts will be __________ kV









  1. View Hint View Answer Discuss in Forum

    v = ia
    L
    = 10√
    1
    = 100 kv
    C0.01 × 10-6

    Correct Option: B

    v = ia
    L
    = 10√
    1
    = 100 kv
    C0.01 × 10-6