Power systems miscellaneous
- If a 100V/10V, 50 VA transformer is converted to 100/110V auto transformer, then rating of the auto transformer is _______ VA
-
View Hint View Answer Discuss in Forum
NA
Correct Option: D
NA
- A transformer rated for 500 kVA. 11 kv/0.4 kV has an impedance at 10% and is connected to an infinite bus. The fault level of the transformer is ___________ kVA
-
View Hint View Answer Discuss in Forum
NA
Correct Option: B
NA
- A 100/5 A bar primary current transformer supplies an O/C relay set at 25% pick up and it has a burden at 5 VA. The secondary voltage is _________V
-
View Hint View Answer Discuss in Forum
NA
Correct Option: A
NA
- If the inductance and capacitance of a system are 1 H and 0·01 μF respectively and the instantaneous value of current interrupted is 10 amps. The value of shunt resistance across the breaker for critical damping is ________ kΩ
-
View Hint View Answer Discuss in Forum
For critical damping,
R = 0.5 √ L = 0.5√ 1 = 5 kΩ C 0.01 × 10-6 Correct Option: C
For critical damping,
R = 0.5 √ L = 0.5√ 1 = 5 kΩ C 0.01 × 10-6
- If the inductance and capacitance of a system are 1·0 H and 0·01 μF respectively and the instantaneous value of current interrupted is 10 amp, the voltage across the breaker contacts will be __________ kV
-
View Hint View Answer Discuss in Forum
v = ia √ L = 10√ 1 = 100 kv C 0.01 × 10-6 Correct Option: B
v = ia √ L = 10√ 1 = 100 kv C 0.01 × 10-6