Power systems miscellaneous


  1. The A, B, C, D constants of a 220 kV line are:
    A = D = 0.94 ∠1°,
    B = 130 ∠73°,
    C = 0.001 ∠90°
    If sending end voltage of the line for a given load delivered at nominal voltage is 240 kV, then % voltage regulation of the line is









  1. View Hint View Answer Discuss in Forum

    Voltage at sending-end,
    Vs = AVR + BIR
    at no-load,
    IR = 0
    and

    VRO =
    Vs
    =
    240
    A0.94∠1°

    = 255.32 Volts
    % voltage regulation =
    VRO - VRL
    × 100
    VRL

    Where VRL is the full-load voltage at receiving-end
    =
    255032 - 220
    × 100 = 16%
    220

    Correct Option: C

    Voltage at sending-end,
    Vs = AVR + BIR
    at no-load,
    IR = 0
    and

    VRO =
    Vs
    =
    240
    A0.94∠1°

    = 255.32 Volts
    % voltage regulation =
    VRO - VRL
    × 100
    VRL

    Where VRL is the full-load voltage at receiving-end
    =
    255032 - 220
    × 100 = 16%
    220